Where should the boiler deoxygenation agent be added for better effect?

2026-09-16 14:10:31
22131

Dissolved oxygen in boiler systems can cause corrosion of metal inner walls, shorten the service life of equipment, and addBoiler deoxidizerIt is a common way to control the oxygen content in water supply. Many operation and maintenance personnel are concerned about the selection of the addition point of the deoxygenation agent when adding it. The appropriate addition location allows the agent to fully react and improve the deoxygenation effect. This article combines boiler water treatment technology to explain the characteristics and selection principles of different dosing positions.

1、 The core principle of selecting investment points

The primary goal of determining the location for adding boiler deoxygenation agent is to ensure that the agent is fully mixed with the feedwater, reserve sufficient reaction time, and allow the deoxygenation agent to fully react with dissolved oxygen in the water. At the same time, the system temperature should be taken into account. A suitable temperature can accelerate the deoxygenation reaction rate, while avoiding premature decomposition of the reagents or interference from other reagents. The final deoxygenation effect may vary depending on the location of addition, the residence time of the agent, and the water temperature conditions.

2、 Common locations for adding boiler deoxygenation agents

1. Thermal deaerator outlet pipeline (widely used)

Thermal deaerator can remove most of the dissolved oxygen in water, but there will still be a small amount of residual oxygen. Adding deoxidizer to the water supply pipeline before the deaerator effluent reaches the economizer is a commonly used solution.

The water temperature at this location is relatively high, which is conducive to accelerating the deoxygenation reaction. The water flow in the pipeline continues, and the chemicals can quickly mix with the water, giving sufficient time to complete the reaction and reducing the residual oxygen entering the boiler body. This point is suitable for most industrial boilers and can protect the economizer and boiler heating surface, reducing the risk of oxygen corrosion. The dosing device is generally equipped with a dosing pump for continuous quantitative injection.

2. Inlet of boiler feedwater pump

Add on the suction side of the feed pump, and the water flow is stirred by the pump body, resulting in better uniformity of the chemical mixture. But there are certain limitations to this position. Under some working conditions, the bubbles introduced by the agent may affect the operation of the pump. At the same time, if the water temperature is low, the reaction speed will slow down, requiring a longer pipeline stroke to complete the reaction. This point is suitable for small boiler systems and requires an assessment of the risk of pump cavitation.

3. Softened water tank/intermediate water tank

Add deoxidizer to the softened water tank. The water tank has a large volume, allowing the water to settle or flow slowly. The mixing time of the agent is sufficient. The disadvantage is that the water temperature in the tank is low, the deoxygenation reaction rate is slow, and the consumption of chemicals will increase. If the sealing of the water tank is insufficient, the water will come into contact with the air again, reabsorb oxygen, weaken the treatment effect, and generally not be the preferred location.

4. Water supply main pipe in front of the economizer

Similar to the outlet position of the deaerator, it is located at the front end of the economizer, with stable water flow and high temperature. The chemical completes the reaction before entering the heating surface, which can protect the economizer tube bundle from oxygen corrosion. Suitable for continuous operation of medium and large boilers, with convenient installation of dosing interfaces for sampling and monitoring of feedwater oxygen content.

5. It is not recommended to directly add it to the boiler drum

It is not recommended to directly add deoxidizer to the boiler steam drum. After the chemicals enter the steam drum, the residence reaction time is insufficient, and dissolved oxygen has already entered the heating surface of the boiler, causing corrosion and limited deoxygenation effect. It is also easy to cause local enrichment of chemicals in the boiler, increasing the risk of scaling.

3、 Supporting conditions that affect the effectiveness of investment

After selecting the dosing point, corresponding dosing equipment should be provided, and a metering pump should be used for continuous dosing to stably control the amount of medication added. It is recommended to install the outlet of the dosing pipeline in the direction of water flow to promote rapid diffusion and mixing of the chemicals.

After addition, a sampling port needs to be set up downstream of the addition point to monitor the dissolved oxygen index of the water supply, and adjust the dosage of the agent based on the test results. At the same time, pay attention to the system water temperature. If the deoxygenation reaction rate decreases under low temperature conditions, adjust the dosing plan appropriately.

4、 Reference for point selection in different boiler scenarios

For industrial steam boilers that operate continuously, priority should be given to selecting the outlet pipe of the thermal deaerator and the feed main pipe in front of the economizer. A small hot water boiler without a thermal deoxygenation device can be added at the outlet of softened water or the inlet of the feed pump, while keeping the water tank sealed to reduce secondary oxygen absorption. Intermittent operation of boilers requires consideration of water quality changes during the start stop phase and strengthened water quality monitoring during dosing.

5、 Summary

Boiler deoxidizerPrioritize adding water to the feedwater pipeline from the thermal deaerator outlet to the economizer, where the water temperature is suitable, the reaction time of the chemicals is sufficient, and the deoxygenation effect is more stable. For boilers with small non thermal deoxygenation equipment, softened water tanks or feed water pump suction ports can be selected for addition, but attention should be paid to water re oxygenation and pump operation risks. Try to avoid directly adding deoxidizer to the boiler steam drum. After determining the dosing point, cooperate with the metering and dosing device to regularly sample and test the oxygen content of the feedwater, adjust the dosing plan in a timely manner, and reduce the problem of boiler oxygen corrosion.