1、 Thermal deoxygenation equipment failure, resulting in an increase in dissolved oxygen in the feedwater (common)
1. Deaerator malfunction: internal spray plate and packing are damaged and blocked; Insufficient heating steam and unstable pressure; The top exhaust valve is blocked or the opening is too small, which prevents oxygen from being discharged in a timely manner. The dissolved oxygen in the effluent increases significantly, requiring more chemical oxygen scavengers to consume excess oxygen.
2. The vacuum degree of the vacuum deoxygenation system decreases: vacuum pump failure, pipeline leakage, deterioration of deoxygenation effect, and more oxygen in the effluent.
3. The water replenishment temperature is too low, the inflow flow rate suddenly increases, the load fluctuates greatly, and the water does not stay in the deaerator for enough time to remove oxygen.
2、 The system is exposed to air, resulting in an increase in oxygen leakage points
1. Air leakage in the negative pressure section of the condensate/drain recovery system: The condenser, drain tank, valve, flange, and pump shaft seal are damaged, and a large amount of air infiltrates, bringing in additional oxygen.
2. The breathing valve of the desalination water tank and soft water tank fails, and air continues to dissolve into the supply water; The water level in the water tank has been low for a long time, and the contact area between the liquid level and the air has increased, resulting in an increase in the oxygen content of the makeup water.
3. Leakage and air intake from the negative pressure side welds, sampling tubes, and instrument interfaces of the pipeline.
3、 Changes in water quality components, additional consumption of deoxidizer
1. Increased hydration hardness: Calcium and magnesium ions will consume sodium sulfiteDeoxidizerThe formation of calcium sulfite precipitation results in additional loss of reagents, especially in the low-pressure boiler sodium sulfite system.
2. More iron ions, copper ions, and oxidative impurities in the water: Metal ions catalyze the oxidation of oxygen scavengers, accelerating the decomposition and consumption of the agents.
3. Low pH of feedwater: The reaction rate of deoxygenating agents (such as hydrazine, DEHA, isoascorbic acid, etc.) decreases, forcing an increase in dosage to maintain residual levels; An increase in carbon dioxide content will also lower the pH, indirectly increasing the consumption of chemicals.
4. Increase in the proportion of make-up water: The proportion of original recovered condensate water is high (condensate water has low oxygen content). Once the recovery of condensate water decreases and the proportion of new make-up water increases, the total dissolved oxygen in the system increases and the dosage of chemicals increases.
4、 Problems with the dosing system and the medication itself
1. Metering pump failure: pump diaphragm damage, one-way valve leakage, pump stroke drift, unstable actual feeding; The automatic dosing system instrument (dissolved oxygen/hydrazine online meter) drifts and readings are low, and the control system continues to increase the dosing amount.
2. Decreased quality of pharmaceuticals: expired storage of pharmaceuticals, deterioration after dilution, insufficient concentration, less effective ingredients under the same dosage volume, and an increase in apparent dosage.
3. Inappropriate dosing location: The injection point of the medication is too far back, and the reaction time is insufficient. The only way to ensure residue is to increase the dosage.
5、 Increased corrosion products in the system, additional consumption of reducing agents
Oxygen corrosion occurs in the system pipeline and economizer, generating a large amount of iron oxide. Iron oxide is an oxidizing substance that will continue to consume reducing propertiesDeoxidizerThis situation is generally accompanied by an increase in iron content in the water, which will exacerbate corrosion in the long run.
Simple troubleshooting sequence
1. Analyze the dissolved oxygen at the outlet of the deaerator, pH of the feedwater, iron ions, and hardness to confirm if the dissolved oxygen exceeds the standard.
2. Check the steam pressure, temperature, and oxygen discharge of the deaerator, and inspect the vacuum system.
3. Check if there is any air leakage in the condensate, drain, and negative pressure section of the water tank.
4. Check the water replenishment ratio and changes in the quality of the replenishment water.
5. Verify the dosing metering pump and online instruments, and test the effective concentration of the chemical.
6. Monitor the iron content in the water supply to determine if there are any corrosive products consuming chemicals.